Had a 200 amp main breaker trip on a brand new panel in a Denver remodel last month. The whole house went dark right after we powered up.
3 comments
Log in to join the discussion
Log In3 Comments
jesse7731mo ago
That 200 amp main tripping right after power up is a classic sign. Wesley139 is right about checking lugs, but a loose factory connection usually causes heat damage over time, not an instant trip. An immediate trip like that points more to a dead short or a ground fault somewhere in the new wiring. I'd be looking real close at any home runs you just landed in that panel before it was energized.
9
wesley1392mo ago
Yeah, loose factory lugs. My buddy had that happen on a new build, turned out a leg was barely hanging on.